MEDIUM VOLTAGE SWITCHGEAR SYSTEM NES
Draw-out type switchgear for indoor installation, type-tested, factory-assembled, air-insulated, metal-enclosed with a fourfold compartment.
Compact panel for contactor feeder that is 500mm wide.
Application as a single bus system or as a duplex system.
Optional: motor-operated withdrawable units and earthing switches
The following variations are possible for the conduction of hot gases that result from arc faults:
- deflector plate
- arc absorber
- pressure release duct
Technical Data
Rated values | up to | |
rated voltage | 12 | kV |
rated power-frequency withstand voltage | 28 | kV |
rated lightning impulse withstand voltage | 75 | kV |
rated busbar current | 2.500 | A |
rated short-time withstand current | 40 | kA |
rated peak withstand current | 100 | kA |
rated short-circuit duration | 3 | s |
internal arc fault test 1s ** | 40 | kA |
Dimensions | |||||
cubicle width | 1.000 | 800 | 650 | 500 | mm |
cubicle depth* | 1.300 | 1.300 | 1.300 | 1.300 | mm |
cubicle height | 2.300 – 2.500incl. control compartment H = 600 up to 800 | mmmm | |||
rated branch currentup to | 2.500 | 2.000 | 1.100 | 350 | A |
* plus 92mm for front door and back wall
** tested contactor panel 40 kA/0,1s
Further values upon request