NES-H18

MEDIUM VOLTAGE SWITCHGEAR SYSTEM NES-H18

Draw-out type switchgear for indoor installation, type-tested, factory-assembled, air-insulated, metal-enclosed with a fourfold compartment.

Circuit breaker in truck types starting at 3.150 A.

Application as a single bus system or as a duplex system.

Optional: motor operated withdrawable units and earthing switches.

The following variations are possible for the conduction of hot gases that result from arc faults:

 

  • deflector plate
  • pressure release duct

Technical Data

 

Rated values up to up to
rated voltage 12 17,5 kV
rated power-frequency withstand voltage 28 38 kV
rated lightning impulse withstand voltage 75 95 kV
rated busbar current 4.000 4.000 A
rated short-time withstand current 55 50 kA
rated peak withstand current 137,5 125 kA
rated short-circuit duration 3 3 s
internal arc fault test 1s 50 50 kA

 

Dimensions
cubicle width* 1.000 1.000 800  mm
cubicle depth** 1.800 1.800 1.800  mm
cubicle height 2.300 – 2.500incl. control compartment H = 600 up to 800  mmmm
rated voltage 17,5 17,5 17,5  kV
rated voltage switchgear 3.150 4.000 A
rated branch current up to: (natural-/air cooled) 3.150 3.400 2.500  A
rated branch current up to:(forced ventilation) 4.050 4.200 3.300  A

 

* plus 77mm for front door and back wall
Further values upon request.