MEDIUM VOLTAGE SWITCHGEAR SYSTEM NES-D
Draw-out type switchgear system for indoor installation, type-tested, factory-assembled, air-insulated, metal-enclosed with an eightfold compartment, double busbar system.
Optional: motor operated withdrawable units, circuit breaker/disconnector and earthing switches.
For the conduction of hot gases that result from arc faults, the switchgear system is equipped with internal pressure release ducts. Optional: conduction out of the control room or a release in the control room with an accumulative absorber.
Technical Data
Rated values | up to | |
rated voltage | 12 | kV |
rated power-frequency withstand voltage | 28 | kV |
rated lightning impulse withstand voltage | 75 | kV |
rated busbar current | 2.500 | A |
rated short-time withstand current | 31,5 | kA |
rated peak withstand current | 80 | kA |
rated short-circuit duration | 3 | s |
internal arc fault test 1s | 31,5 | kA |
Dimensions | |||||
cubicle width | 1.000 | 800 | 650 | mm | |
cubicle depth* | 1.700 | 1.700 | 1.700 | mm | |
cubicle height | 2.825 | 2.825 | 2.825 | mm | |
rated branch current: | 2.500 | 1.100 | 630 | A |
* plus 77mm for doors
Further values upon request