NES-COM

MEDIUM VOLTAGE SWITCHGEAR SYSTEM NESCOM

Draw-out type switchgear for indoor installation, type-tested, factory-assembled, air-insulated, metal-enclosed with a fourfold compartment.

Application as a single bus system or as a duplex system.

Optional: motor operated withdrawable units and earthing switches.

The following variations are possible for the conduction of hot gases that result from arc faults:

 

  • deflector plate
  • arc absorber
  • pressure release duct

Technical Data

 

Rated values up to
rated voltage 17,5 kV
rated power-frequency withstand voltage 38 kV
rated lightning impulse withstand voltage 95 kV
rated busbar current 2.500 A
rated short-time withstand current 40 kA
rated peak withstand current 100 kA
rated short-circuit duration 3 s
internal arc fault test 1s 40 kA

 

Dimensions
cubicle width 800 600  mm
cubicle depth 1.300 1.300  mm
cubicle height 2.200 2.200  mm
rated feeder current 2.500 1.250  A